The device for accurate, reliable biogas measurement with loop-powered technology. Inline flowmeter designed for measurement of wet biogas and digester gas under fluctuating process conditions.
|
|
Sensor Features
|
Optimized for low pressure gas – specialized sensor design. No additional pressure loss – full-bore design. Process transparency – diagnostic capability. Multivariable device: flow, temperature and methane. Medium temperature: 0 to 80 °C (32 to 176 °F). Process pressure: 0.7 to 11 bar a (10.2 to 159 psi a).
|
|
Transmitter Features
|
Convenient device wiring – separate connection compartment. Safe operation – no need to open the device due to display with touch control, background lighting. Integrated verification – Heartbeat Technology. Loop-powered technology. Robust dual-compartment housing. Plant safety: worldwide approvals.
|
|
Nominal Diameter Range
|
Single‐path version: DN 50 (2"), DN 80 (3") Two‐path version: DN 100 to 200 (4 to 8")
|
|
Wetted Materials
|
Sensor: 1.4404/1.4435 (316L) Transducer: HNBR Temperature sensor (option): AFM 34
|
|
Measured Variables
|
Volume flow, corrected volume flow, corrected methane volume flow, energy flow, methane fraction, calorific value, temperature
|
|
Max. Measurement Error
|
Volume flow (standard): ‐ ±1.5 % o.r. for 3 to 30 m/s (9.84 to 98.4 ft/s) ‐ ±3 % o.r. for 1 to 3 m/s (3.28 to 9.84 ft/s) Volume flow (option): ‐ ±0.1 % o.f.s. for 0.3 to 1 m/s (0.98 to 3.28 ft/s) ‐ ±1.5 % o.r. for 1 to 30 m/s (3.28 to 98.4 ft/s)
|
|
Measuring Range
|
Standard: 1 to 30 m/s (3.28 to 98.4 ft/s) Option: 0.3 to 30 m/s (0.98 to 98.4 ft/s)
|
|
Max. Process Pressure
|
11 bar a (159 psi a)
|
|
Medium Temperature Range
|
0 to +80 °C (+32 to +176 °F)
|
|
Ambient Temperature Range
|
Flange material carbon steel: –10 to +60 °C (+14 to +140 °F) Flange material stainless steel: –40 to +60 °C (–40 to +140 °F)
|
|
Transmitter Housing Material
|
AlSi10Mg, coated; 1.4404 (316L)
|
|
Degree Of Protection
|
IP66/67, type 4X enclosure
|
|
Display/Operation
|
4‐line backlit display with touch control (operation from outside) Configuration via local display and operating tools possible
|
|
Outputs
|
4‐20 mA HART (passive) 4‐20 mA (passive) Pulse/frequency/switch output (passive)
|
|
Inputs
|
Current input 4‐20 mA (passive)
|
|
Digital Communication
|
HART
|
|
Power Supply
|
DC 12 to 35 V (4‐20 mA HART with/without pulse/frequency/switch output) DC 12 to 30 V (4‐20 mA HART, 4‐20 mA) DC 12 to 35 V (4‐20 mA HART, pulse/frequency/switch output, 4‐20 mA input) DC 9 to 32 V (PROFIBUS PA, pulse/frequency/switch Output)
|
|
Hazardous Area Approvals
|
ATEX, IECEx, cCSAus, NEPSI, INMETRO, JPN
|
|
Metrological Approvals And Certificates
|
Calibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
|
|
Pressure Approvals And Certificates
|
PED
|
|
Material Certificates
|
3.1 material (wetted parts)
|